Professional China Imc Pipe - Electrical Conduit Pipe EMT – Rainbow
Professional China Imc Pipe - Electrical Conduit Pipe EMT – Rainbow Detail:
Electrical Metallic Tubing
Electrical metallic tubing (EMT), also commonly called thin-wall, is a listed steel raceway of circular cross section, which is unthreaded, and nominally 10′ long. 20′ lengths are also available. EMT is available in trade sizes 1/2 through 4. The outside is galvanized for corrosion protection and the inside has an approved corrosion-resistant organic coating. EMT is installed by use of set-screw or compression-type couplings and connectors. It is permitted to have an integral coupling comprised of an expanded, “belled” shape tube on one end with set screws. EMT with integral couplings is available in trade sizes 1-1/4 through 4.
Applicable Tolerance:
Outside Diameter : ±0.005in(0.13 mm)
Wall Thickness: +10%~ -5%
The wall thickness shall not vary more than 0.003in(0.08mm) throughout a 10 foot length
Length:±0.25 in (6.4 mm)
Standard: UL797-2000
Finishes: Zinc Plated, Pre-galvanized
Zinc coated: class 3, 80-120 g/m2; class 4, 275-500 g/m2
Package: 1.Big OD: in bulk;
2.Small OD: in bundles, packed by steel strips;
3.Waterproof package with plastic cloth;
4.Standard export package;
5.According to customers’ requirements.
Size |
Outside Diameter |
Inside Diameter |
|
|
||||
inch |
inch |
mm |
inch |
mm |
(1)mm |
(2)mm |
feet |
mm |
1/2” |
0.706 |
17.93 |
0.622 |
15.80 |
1.07 |
0.85 |
10 |
3050 |
3/4” |
0.922 |
23.42 |
0.824 |
20.93 |
1.25 |
1.00 |
10 |
3050 |
1” |
1.163 |
29.54 |
1.049 |
26.64 |
1.45 |
1.10 |
10 |
3050 |
1-1/4” |
1.510 |
38.35 |
1.380 |
35.05 |
1.65 |
1.30 |
10 |
3050 |
1-1/2” |
1.740 |
44.20 |
1.610 |
40.89 |
1.65 |
1.30 |
10 |
3050 |
2” |
2.197 |
55.80 |
2.067 |
52.50 |
1.65 |
1.40 |
10 |
3050 |
2-1/2” |
2.875 |
73.00 |
2.731 |
69.37 |
1.83 |
- |
10 |
3050 |
3” |
3.500 |
88.90 |
3.356 |
85.24 |
1.83 |
- |
10 |
3050 |
3-1/2” |
4.000 |
101.60 |
3.834 |
97.38 |
2.11 |
- |
10 |
3050 |
4” |
4.500 |
114.30 |
4.334 |
110.08 |
2.11 |
- |
10 |
3050 |
Applications:
Conduit pipe is generally installed by electricians at the site of installation of electrical equipment. It is used to protect and route electrical wiring in a building or nonbuilding structure.
Product detail pictures:
Related Product Guide:
Some problems in the construction of steel structure and their solutions
Greenhouse commonly used steel greenhouse introduction
"Based on domestic market and expand overseas business" is our development strategy for Professional China Imc Pipe - Electrical Conduit Pipe EMT – Rainbow , The product will supply to all over the world, such as: USA, Burundi, Bangalore, Our business activities and processes are engineered to make sure our customers have access to widest range of products with the shortest supply time lines. This achievement is made possible by our highly skilled and experienced team. We look for people who want to grow with us around the globe and stand out from the crowd. We have people who embrace tomorrow, have vision, love stretching their minds and going far beyond what they thought was achievable.
By Maxine from Porto - 2018.12.10 19:03
Good quality and fast delivery, it's very nice. Some products have a little bit problem, but the supplier replaced timely, overall, we are satisfied.
By Adam from Italy - 2018.12.30 10:21