Electrical Metallic Tubing
Electrical metallic tubing (EMT), also commonly called thin-wall, is a listed steel raceway of circular cross section, which is unthreaded, and nominally 10′ long. 20′ lengths are also available. EMT is available in trade sizes 1/2 through 4. The outside is galvanized for corrosion protection and the inside has an approved corrosion-resistant organic coating. EMT is installed by use of set-screw or compression-type couplings and connectors. It is permitted to have an integral coupling comprised of an expanded, “belled” shape tube on one end with set screws. EMT with integral couplings is available in trade sizes 1-1/4 through 4.
Applicable Tolerance:
Outside Diameter : ±0.005in(0.13 mm)
Wall Thickness: +10%~ -5%
The wall thickness shall not vary more than 0.003in(0.08mm) throughout a 10 foot length
Length:±0.25 in (6.4 mm)
Standard: UL797-2000
Finishes: Zinc Plated, Pre-galvanized
Zinc coated: class 3, 80-120 g/m2; class 4, 275-500 g/m2
Package: 1.Big OD: in bulk;
2.Small OD: in bundles, packed by steel strips;
3.Waterproof package with plastic cloth;
4.Standard export package;
5.According to customers’ requirements.
Size |
Outside Diameter |
Inside Diameter |
|
|
||||
inch |
inch |
mm |
inch |
mm |
(1)mm |
(2)mm |
feet |
mm |
1/2” |
0.706 |
17.93 |
0.622 |
15.80 |
1.07 |
0.85 |
10 |
3050 |
3/4” |
0.922 |
23.42 |
0.824 |
20.93 |
1.25 |
1.00 |
10 |
3050 |
1” |
1.163 |
29.54 |
1.049 |
26.64 |
1.45 |
1.10 |
10 |
3050 |
1-1/4” |
1.510 |
38.35 |
1.380 |
35.05 |
1.65 |
1.30 |
10 |
3050 |
1-1/2” |
1.740 |
44.20 |
1.610 |
40.89 |
1.65 |
1.30 |
10 |
3050 |
2” |
2.197 |
55.80 |
2.067 |
52.50 |
1.65 |
1.40 |
10 |
3050 |
2-1/2” |
2.875 |
73.00 |
2.731 |
69.37 |
1.83 |
- |
10 |
3050 |
3” |
3.500 |
88.90 |
3.356 |
85.24 |
1.83 |
- |
10 |
3050 |
3-1/2” |
4.000 |
101.60 |
3.834 |
97.38 |
2.11 |
- |
10 |
3050 |
4” |
4.500 |
114.30 |
4.334 |
110.08 |
2.11 |
- |
10 |
3050 |
Applications:
Conduit pipe is generally installed by electricians at the site of installation of electrical equipment. It is used to protect and route electrical wiring in a building or nonbuilding structure.
Product detail pictures:
Related Product Guide:
Some problems in the construction of steel structure and their solutions
Greenhouse commonly used steel greenhouse introduction
Innovation, excellent and reliability are the core values of our firm. These principles today more than ever form the basis of our success as an internationally active mid-size corporation for 2019 wholesale price Electrical Gi Conduit Pipes - Electrical Conduit Pipe EMT – Rainbow , The product will supply to all over the world, such as: Swiss, Barcelona, Colombia, We have customers from more than 20 countries and our reputation has been recognized by our esteemed customers. Never-ending improvement and striving for 0% deficiency are our two main quality policies. Should you need anything, don't hesitate to contact us.
By Princess from Greece - 2018.10.31 10:02
This is a reputable company, they have a high level of business management, good quality product and service, every cooperation is assured and delighted!
By Klemen Hrovat from Denver - 2017.03.08 14:45